COMPACT FIXED( C.F):

 

  • It means Air-Insulated. The air is used at these switchgears around bus-bars within voltage range (1-36kv). Entire main equipment of AIS switchgear is in contact with their surrounding air. Structure of this kind of switchgear, including several isolated units (cells), is put together.   

 

NOTE Specifications         
ROW
 COMPACT FIXED(C.F)
Name of Switchgear 1
Standing Type of switchgear
2
                                20KV
Nominal voltage
3
50HZ  Nominal frequency
4
630A Nominal current
5
  3 Number of system phases 6
 24KV                                                 System maximum voltage
7
IEC62271 Production standard 
8
IP 2X – as per IEC60259 Standard Protection degree
9
 Bottom  Access to input and output cables
10
 One-way (of front)
 Switchgear access
11
 75-100  Power key cell  12

Dimensions of switchgear
  75       Calibration instruments 13
50                           Riser cell  14
75                 Bus-coupler cell 15

Under-load breakable sectioner cell 50-37.5

16
50         Fusible sectioner cell 17
90-100                 Depth (cm) 18
    165              Height (cm)  19
 RAL 7032-7035  Color (front gate) 20
 * Potential for automation 21
16 KA-25kv 
 Minimum nominal current of IK short circuit 22
 1s-3s  Minimum nominal time for short circuit (TK) 23
(16KA)2.5 equal to IK The minimum nominal peak withstand current 24
                                                                    Contact at contact at closed mode: 125 KVPN
Contact at open mode: 145 KVP
 Minimum voltage tolerance against thunder impact 25
 Contact at closed mode: 50 kv
Contact at open mode: 60 kv

 Minimum voltage tolerance at network frequency for one minute 26
 Galvanized   Type of body cover           
27
 2Mm     Diameter of plate   
28
 Vacuum-gas  Type of power keys (circuit breaker) 29
 Sf6 gas  Type of sectioner  30